PRODUCT OVERVIEW
TOMAR Electronics 4374S offers Steady-burn and Single or Double Flash mode in a single unit. The operating modes can be easily configured with either internal DIP switch, or external wire selection. TOMAR 4374S features efficient lens optics coupled with an LED array with light output which rivals that of a strobe.
The model 4374S is UL and cUL listed for Class I, Division 2, Groups A, B, C, and D; Class II, Division 2, Groups F and G; Class III.
Application Locations
Typical applications include manufacturing plants, chemical and petrochemical processing facilities, sewage treatment plants, off-shore and dockside installations, agricultural food processing, industrial, mining, and marine offshore facilities.
The 4374S is NEMA 4X rated and constructed to IP66. It is water-tight, dust-tight, and corrosive resistant. It can be operated in any orientation, and features a ¾” ISP pendant mount.
Key Features
- Class I, Div. 2 Groups A, B, C, & D
- Class II, Div. 2 Groups F & G
- 2-year warranty on power supply
- NEMA 4X
- UL Listed
- CSA Certified
- 100,000 Hours strobe tube
- 6 lens colors
- UL 1598 Impact resistant polycarbonate lens
- Available lens guard (4375-Guard)
Specs
- Operating Voltage: 12-74 DC
- Operating Temperature: -55°C to 66°C
- Voltage and Amperage:
- 12-74 VDC draws 1.2 Amps at 12 VDC;
- 590mA at 24 VDC;
- 370mA at 48 VDC;
- 190mA at 80 VDC
- Inrush Current: ≤ 1.75 Amps @ 24 VDC
- Flash Rates/Operation: 80 SFPM
- Candela Effective: 200 Cd-Eff
- Size and Weight: 0.5” tall x 5.4” dia. x 3.2 lbs (215mm x 137mm x 1.45kg)
Architect and Engineer Specifications
Hazardous Location visual signaling beacon shall be Tomar model number series 4374S or approved equal. The beacon shall be UL Listed and CSA approved Class I, Division II, Groups A, B, C, and D; Class II, Div. 2, Groups F & G; Class III for use in specified hazardous locations as classified by the National Electric Code. The light source shall be constructed with 4-wire and supervisory circuits. The warning signal must consume no more than 1.75 Amps inrush current. Voltage ranges shall be 12-74 VDC. The warning light shall be rated NEMA 4X and have a field-replaceable polycarbonate lens assembly. Lens shall meet UL 1598 impact resistance standards.
Helpful Links
3D STEP FILES
FAQ's
Will a 120vac light work on 110vac? A 240vac unit on 220vac?
Yes, operating voltage is actually +/- 10% of rated voltage.
Can I use a replacement 8 pin Tomar strobe tube in another manufacturers fixture if it physically fits?
No, the strobe tube should be matched to the model of the strobe light
Are your ½” male and female pipe mounts NPT, or another thread type (i.e. straight conduit)?
Our male and female pipe mounts are NPT
Where can I find the product data sheets
Click here to access our product data sheets